Air sampling smoke detection system
TITANUS SuperSens
Quick Guide for Commissioning
1 Installation
§
Connect power (24V)
§
Connect outputs for info- (AL1), pre- (AL2) and mainalarm (AL3) as well as “fault”
(switchover relay contacts)
§
Connect reset input
§
Connect ext. input “night” (alt.Sens.) (if required)
§
Connect pipe system or test pipe
2 Set
Up
Set DIP switches on pcb “basis E603.1” according to tables below:
Air flow monitoring
switch
Delay time
Switch
range
S2
S2
A(1)
B(2)
C(3)
D(4)
OFF
ON
Short
30 s
ON
OFF
small
I
ON
OFF
Middle
2 min.
(standard)
OFF
ON
middle
II
ON
ON
Long
15 min.
OFF
OFF
large
III
(standard)
OFF
OFF
very long
1 h
ON
ON
very large
IV
Alarm
switch
Delay time
Switch
sensitivity
S2
S2
E(5)
F(6)
G(7)
H(8)
OFF
ON
Short
0 s
ON
ON
0,2 %/m
I
ON
OFF
Middle
10 s
(standard)
OFF
ON
0,1 %/m
II
(standard)
OFF
ON
Long
30 s
ON
OFF
0,05 %/m
III
ON
ON
very long
60 s
OFF
OFF
0,025 %/m
IV
Fault
switch
S2
J(10)
OFF
Fault not latching
(standard)
ON
Fault latching until reset
Atmospheric pressure compensation
R58
MP1 (+)
MP2 (-)
see correction table for atm.pressure
or
2,50 V
(standard)
Fire & Security Products
Siemens Building Technologies Group