Air sampling smoke detection system
TITANUS SuperSens

Quick Guide for Commissioning

1 Installation

§

  Connect power (24V)

§

  Connect outputs for info- (AL1), pre- (AL2) and mainalarm (AL3) as well as “fault”

(switchover relay contacts)

§

  Connect reset input

§

  Connect ext. input “night” (alt.Sens.) (if required)

§

  Connect pipe system or test pipe

2 Set 

Up

Set DIP switches on pcb “basis E603.1” according to tables below:

Air flow monitoring

switch

Delay time

Switch

range

S2

S2

A(1)

B(2)

C(3)

D(4)

OFF

ON

Short

30 s

ON

OFF

small

I

ON

OFF

Middle

2 min.

 (standard)

OFF

ON

middle

II

ON

ON

Long

15 min.

OFF

OFF

large

III        

(standard)

OFF

OFF

very long

1 h

ON

ON

very large

IV

Alarm

switch

Delay time

Switch

sensitivity

S2

S2

E(5)

F(6)

G(7)

H(8)

OFF

ON

Short

0 s

ON

ON

0,2 %/m

I

ON

OFF

Middle

10 s

 (standard)

OFF

ON

0,1 %/m

II         

(standard)

OFF

ON

Long

30 s

ON

OFF

0,05 %/m

III

ON

ON

very long

60 s

OFF

OFF

0,025 %/m

IV

Fault

switch

S2
J(10)

OFF

Fault not latching        

(standard)

ON

Fault latching until reset

Atmospheric pressure compensation

R58

MP1 (+)

MP2 (-)

see correction table for atm.pressure

or

2,50 V 

(standard)

Fire & Security Products

Siemens Building Technologies Group