Fire Safety & Security Products
Building Technologies
1583_o_en_−−_2
21
08.2005
2.4
Panel preparation FC330A-x (4 loops)
Pull out with screwdriver in
order to detach the relay
module from the profile rail
Place batteries and inserted jumper ”ST8/9 or ST10”
according to the battery make used
ST8
Yuasa
ST9
ALARMCOM (default) / Power sonic
ST10
Sonnenschein (more info see page 106)
Insert EPROMs
Insert inscription stripes
Snap the Z3B171 relay on
to the profile rail
If mains voltage 230/115VAC is applied for con-
trols, fasten cables with cable tie and stick
warning label close to the relay units
4
1
2
EP2
EP1
Either AX1212 (12Ah) or AX1210 (15Ah)
depending on emergency power requirement
(or equivalent but max. 17Ah)
External voltage
side (contacts)
3
or
Control unit voltage side (coil)
124mm
max. 8 relays possible
extension 122mm (474908)
ST8
ST9
ST10
Master board
(K3X020)
or
only with
FC330A−2/-2-CH/-5
Danger
external voltage
B3R080
AX1210
AX1210
AX1212
AX1212