
Fire Safety & Security Products
Building Technologies
1583_o_en_−−_6
106
08.2005
6.1.2
Emergency power battery
The charger of the FC330A−x is designed to charge the emergency power battery up to
80% of it’s nominal capacity within 24h.
− Compatible sizes: 2x12V/12Ah or 2x12V/15Ah or 2x17Ah or 4x12V/12Ah by using
Z3I1020
Restriction:
The quiescent current shall not exceed 500mA if a higher quie-
scent current is needed use the additional power supply Z3I1000
6.1.3
Required battery capacity for standard configurations
Configuration
Quiescent
current
12h
(f 1.1 + f1.25)
24h
(f 1.25)
72h
FC330A-ECO.. with 100 AnalogPLUS detectors
120mA
1,98Ah
3,60Ah
8,64Ah
FC330A−x
with 200 AnalogPLUS detectors
168mA
2,77Ah
5,04Ah
12,09Ah
FC330A−x
with 300 AnalogPLUS detectors
190mA
3,13Ah
5,70Ah
13,68Ah
FC330A−x
with 400 AnalogPLUS detectors
210mA
3,46Ah
6,30Ah
15,12Ah
FC330A−x
with 500 AnalogPLUS detectors
230mA
3,79Ah
6,90Ah
16,56Ah
FC330A−x
with 500 AnalogPLUS detectors
and 4 conv. lines, fully loaded
255mA
4,20Ah
7,65Ah
18,36Ah
Remarks:
t
he indicated values are understood with fault signal due to mains failure in state acknowledged
LCD-backlight not lit (timeout expired)
for discharge over a
≤
24h period multiplied by factor 1.25 (according to DIN VDE 0933, part 2)
for discharge over a
≤
12h period additionally multiplied by factor 1.1 (additional loss of capacity of 9%)
alarm current for sounders, remote transmission device etc. not included (in most countries also an alarming period of 10 ... 30min with the
effective connected alarm sounders, remote transmission device etc. has to be included)
add-on cards not included
6.1.4
System voltage
The system voltage during mains supply depends on
a) position of jumper ‘ST3’
⇒
temperature compensation ON or OFF
b) position of jumper ‘ST8/9/10’
⇒
used battery make
(Sonnenschein or PowerSonic (Alarmcom) or Yuasa)
c) ambient temperature
⇒
providing the temperature compensation is ON
If jumper ‘ST3’ is set to position
‘bottom’
⇒
temperature compensation ON see table below
‘top’
⇒
temperature compensation OFF voltage is fixed at 25
°
C
Temperature
SONNENSCHEIN
POWER SONIC
YUASA
Jumper ST10 inserted
Jumper ST9 inserted
Jumper ST8 inserted
0
°
C
29.14V
27.90V
28.20V
25
C (‘ST3’ = OFF)
27.40V
27.20V
27.30V
50
°
C
26.56V
26.61V
26.40V