22/52
Building Technologies
Bus operator unit RMZ792
CE1P3113en
HVAC Products
6 “Commissioning” menu
03.04.2006
6.1.4 Error
handling
Error
Cause / remedy
No communication with other bus users
The device address is 255, which means
that communication is not active.
Set the device address to a value be-
tween 1 and 252 (automatic search or
manual predefinition).
The subnetwork address (area or line) of
the line couplers and / or the bus users do
not correspond.
Check the subnetwork addresses or
reassign them.
The subnetwork address (SNA) has not
been adopted by the superposed line
coupler
There is no superposed line coupler, or
the line coupler is configured in a way that
it does not send the SNA to the line.
Configure the line coupler accordingly or
predefine the SNA manually.
Fault status message
6001 >1 identical bus address
There are several bus users with identical
device addresses on the network. Correct
the device addresses on the respective
devices accordingly.
6.2 Activating
communication
Communication is activated when:
•
The device has a valid device address
•
Bus power supply is available
•
The device is not on the commissioning menu
6.2.1 Submenu
“Communication”
A detailed description of communication is given in Basic Documentation P3127 “Com-
munication via Konnex bus”. Basic knowledge of device addresses and network to-
pologies is a prerequisite here.
Main menu > Commissioning > Communication
Operating line
Range
Factory setting
Area 0…15
0
Line 0…15
2
Device address
1…255
255
Search address
--- / Address found
---
Programming mode
Off / On
Off
Setting values
Area
,
Line
and
Device address
are used to manually create individual
device addresses.
Automatic address search is triggered via operating line
Search address
. A successful
address search is acknowledged with status
Address found
. Status
Address failed
indi-
cates that the address search has been unsuccessful.
For assigning addresses via the ETS, the programming mode must be set to
On
. After
successful address assignment, the ETS will automatically switch the value back to
Off
.
•
If a line coupler superposed in the network topology delivers SNA information other
than the values set for the area and the line, the line coupler’s values will be adopted
•
If 2 devices have identical device addresses, an error message will be delivered
Possible cases
General
Operating lines
Notes