August 2007
Door / Window Contact Smoke Detector
Mounting Auxiliary Equipment
Mounting the Smoke Detector
Mounting location DELTA reflex smoke detector
When choosing the mounting location for the smoke
detector, the following points must be observed:
Every smoke detector can cover an area of
max. 60 m
2
Fit the smoke detector as close as possible to
the center of the ceiling (minimum distance from
wall and corner: 15 cm)
In rooms with inclined or pointed ceilings, fit the smoke detector
approx. 90 cm from the highest point of the ceiling
In the case of rooms having a height of more than 3 m, several smoke
detectors are required (mounting height on the wall = 2.5 m)
Take air flows into account (depending on the type of house)