67/88
Siemens Synco
900
CE1C2707en
Building Technologies
Function settings
05.07.2007
Main menu > Heating > Room X > Room settings >
Valve pos cooling:
Room
number
1 2 3 4 5 6
Room
name
Factory setting
0 %
0 %
0 %
0 %
0 %
0 %
Setting
Room
number
7 8 9 10 11 12
Room
name
Factory setting
0 %
0 %
0 %
0 %
0 %
0 %
Setting
The setting has the following effect in dependence of the
actuator type used:
RRV912:
3-point actuator
The actuator exactly arrives at the set position.
RRV918 / RRV912:
2-point actuator (NC / NO)
The actuator is not controlled with setting 0..49% and remains
in the start position (for NC = 0%).
The actuator is controlled by a permanent pulse with setting
50..100% and thus remains in the end position (for NC = 100%).
SSA955
The actuator exactly arrives at the set position.
Minimum valve position Comfort
To prevent cold floors in the case of floor heating systems, a mini-
mum valve position (0..100 %) can be fixed which is observed during
Comfort periods, even if the room temperature is sufficiently high. It is
accepted that in such cases the room might get overheated.
Main menu > Heating > Room X > Room settings >
Min valve pos comf:
Factory setting
0 %
Your setting
Summary of Contents for Synco 900
Page 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Page 2: ......
Page 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Page 87: ......