7.1.5
Troubleshooting
Fault message "[Time switch 2] failure" is displayed if a time switch signal from the
bus is anticipated and not sent. In this case, the recipient continues to operate on
"On".
No. Text
Effect
5101 [Time switch 1] failure
Non-urgent message; must not be acknowledged
5111
[Time switch 2] failure
Non-urgent message; must not be acknowledged
5121 [Time switch 3] failure
Non-urgent message; must not be acknowledged
5131 [Time switch 4] failure
Non-urgent message; must not be acknowledged
5141 [Time switch 5] failure
Non-urgent message; must not be acknowledged
5151 [Time switch 6] failure
Non-urgent message; must not be acknowledged
Fault messages
7.2
Holidays/special days
Calendar
Plant operators can enter days deviating from the standard 7-day program as
holidays or special days via the "Holidays/special days" menu.
The holidays/special day program is visible only if at least one time switch is active.
7.2.1
Communication
The same holidays/special day program can be assigned to other controllers if
RMS705B communicates with other controllers (see Section 13). Different sources
can be used as the master. Enter this in the RMS705B (see Section 13.2.2
Holidays/special days).
The following settings are possible:
Autonomous (neither sends nor receives).
From bus: Slave (receives holidays/special day program from the bus).
To bus: Master (sends holidays/special day program via bus).
63 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
7-day time switch
01.04.2010