13 Communication
See basic documentation "Communication via KNX bus" (P3127) for a detailed
description of communications.
The following section only describes the most important settings to commission
simple communications.
13.1 Enable communication
Device communication is enabled when:
The device address is entered
(each bus member requires an individual device address).
Bus power supply is available.
RMS705B is not in the Commissioning menu.
13.2 "Communication" menu settings
13.2.1 Basic settings
Main menu > Commissioning > Communication > Basic settings >
Setting values
Operating line
Range
Factory setting
Device address
1...253 (1...255)
255
Decentral bus power supply
Off, On.
On.
Clock time operation
Autonomous, Slave, Master
Autonomous
Remote setting clock slave
Yes, No
Yes
Remote reset of fault
Yes, No
No
View the settings entered here via:
Main menu > Device information > Communication > Basic settings
Each bus member requires a unique device address.
Device address
Device address 255 is used to disable communications
(no exchange of process data).
Notes
If two devices on the KNX bus have the same device address, fault message
">1 identical device address" is displayed.
For small plants, decentralized bus power supply suffices.
Decentral bus power
supply
This is the default setting.
See documents N3127 and P3110 on decentralized bus supply.
Notes
Fault message "No bus power supply" is displayed and communications
interrupted if there is no bus supply.
Access using Service tool OCI700.1 is only possible if communications is
enabled.
182 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Communication
01.04.2010