5
Siemens
A6V11893002_en--_c
Smart Infrastructure
2021-07-05
Test function active
DIP
X1
X2
X3
DIP1 (ON) DIP6 (OFF) DIP7 (OFF)
0 V / 0 V
4 mA
5 V / 2.5 V
12 mA
10 V / 5 V
20 mA
DIP1 (ON) DIP6 (OFF) DIP7 (ON)
5 V / 2.5 V
12 mA
10 V / 5 V
20 mA
0 V / 0 V
4 mA
DIP1 (ON) DIP6 (ON) DIP7 (OFF)
10 V / 5 V
20 mA
0 V / 0 V
4 mA
5 V / 2.5 V
12 mA
DIP1 (ON) DIP6 (ON)
DIP7 (ON)
5 V / 2.5 V
12 mA
5 V / 2.5 V
12 mA
5 V / 2.5 V
12 mA
PM2.5 calibration mode
1)
Function
1
2
OFF
OFF
Mode 1 (default)
OFF
ON
Mode 2
ON
OFF
Mode 3
ON
ON
Reserved
Note:
1)
Mode 1 is for standard use. Mode 2 and Mode 3 are for advanced application.
●
Mode 1: The sensor is calibrated using the TSI device as reference in Arizona A1 dust.
●
Mode 2: The sensor is calibrated using the GRIMM device as reference in Arizona A1
dust.
●
Mode 3: The sensor is calibrated using the GRIMM device as reference in KCL dust.
S2