Command Input/Output
Binary Command Input IFC-P/IFC-D
Input voltage
range
12
DC 24 V to 250 V (tolerance -20 % to
+20 %)
Input per module
4
Nominal Input
Voltage
Typical Threshold Voltage
Tolerance
24 V
17.0 V
+/- 10 %
48 V or 60 V
33.0 V
+/- 10 %
110 V
75.0 V
+/- 10 %
220 V or 250 V
155.0 V
+/- 10 %
Polarity
Independent
Pulse suppression
1 ms to 100 ms (programmable in steps
of 1 ms)
Input current
Max. 2 mA
Binary Command Output IFC-P for normal contact load
Contact type
Relay NO, normally open
Contacts per module
4
Contact material
Ruthenium
Switching power
250 W/250 VA
Switching voltage
AC/DC 250 V
Switching current
AC/DC 1.5 A
Carry current < 2.5 ms
AC/DC 5 A
Carry current
AC/DC 1.5 A
Insulation withstand voltage
AC 3 kV
Contact configuration
Single pole, normally open
Connection cable
≤ 2.5 mm
2
(modular terminal block)
Pickup time including contact-chatter time maximum 2 ms
Electric strength of contacts/coil
AC 3000 V
Binary Command Output IFC-D for high contact load
Contact type
Relay NO, normally open
Contacts per module
4
Contact material
Silver Tin Oxide
Switching power
150 W/1250 VA
Switching voltage
AC/DC 250 V
Switching current
AC/DC 5 A (30 A ≤ 0.5 ms)
Carry current
AC/DC 5 A
Insulation withstand voltage
AC 3 kV
Contact configuration
Single pole, normally open
Connection cable
≤ 2.5 mm
2
(modular terminal block)
Electric strength of contacts/coil
AC 3000 V
14.2
12
Regardless of the configured nominal input voltage, the maximum voltage of DC 287.5 V can be connected.
Technical Data
14.2 Command Input/Output
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
369
C53000-G6040-C605-1, Edition 03.2020