PU4 Firmware Upgrade with Mem Tool
Connecting the PC
In order to program the PU4 module of SWT 3000, use the USB connector of the PU4 module. The connec-
tion to the service PC is established with with the USB connecting cable supplied with the device. The SWT
3000 PU4 CP2102 USB to UART Bridge Controller must have been installed with installation of the service
program PowerSys on the PC (refer to Chapter
5.1.3 Installation of the Service Program PowerSys
).
In order to program the PU4 module, perform the following instructions:
•
Turn off the device with the S2 switch on the PU4 module.
•
To enable the programming with MemTool, set the S3.1 of S3 DIL switch on the PU4 module to ON
position.
•
Turn on the device with the S2 switch on the PU4 module.
•
Press the S1 reset button on the PU4 to proceed the upgrade.
i
i
NOTE
If SWT 3000 is integrated into PowerLink (as iSWT), perform the following instructions:
•
Turn off the device with the S1 switch on the CSPi module.
•
To enable the programming with MemTool, set the S5.2 on the CSPi module to ON position.
•
To enable the programming with MemTool, set the S3.1 of S3 DIL switch on the PU4 module to ON
position.
•
Turn on the device with the S1 switch on the CSPi module.
•
Press the S1 reset button on the PU4 to proceed the upgrade.
!
CAUTION
²
During the update operations with MemTool the device (SWT 3000 or PowerLink with iSWT) will be
out of regular service.
Starting MemTool
In order to launch MemTool as a stand-alone tool, execute Memtool.exe via the Windows main menu Start >
Programs > UDE MemTool.
5.5
5.5.1
5.5.2
PowerSys and Auxiliary Software Tools
5.5 PU4 Firmware Upgrade with Mem Tool
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
239
C53000-G6040-C605-1, Edition 03.2020