Interface
X48
X49
X46
X44
X7
X8
X9
X22
X23
G703.6 symmetric
23-24
33-34
23-24
33-34
1-2
2-3
2-3
2-3
2-3
2-3
2-3
G703.6 asymmetric
25-26
33-34
23-24
33-34
2-3
1-2
1-2
1-2
1-2
1-2
1-2
Selection of the Input Gain for G703.6 Interfaces
This setting controls the sensitivity of the receive equalizer.
Table 3-22
Selection of the Input Gain for G703.6 Interfaces
Input gain
LID-1
LID-2
12 dB (for short haul)
X53 / 2-3
X52 / 2-3
43 dB (for long haul)
X53 / 1-2
X52 / 1-2
DLE Settings for the LID-x Connection via FOM
i
i
NOTE
If there is a connection of the LID-x via fiber-optic modules, always select the X.21 interface on the DLE
module.
When LID-x is connected via fiber-optic modules, no electrical cable must be connected at the corre-
sponding LID-x connector.
Jumper Settings for the CLE Module
[scclejum-301111-01.tif, 1, en_US]
Figure 3-10
Position of the Jumpers on the CLE Module
Table 3-23
Jumper Setting for the Input and Output Impedance
Setting
600 Ω
≥ 5 kΩ
Input impedance
W4
Without W4
Output impedance
W5
W6, W7, W8
3.3.4.4
3.3.4.5
3.3.5
Installation and Commissioning
3.3 Jumper Settings for SWT 3000 Modules
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
115
C53000-G6040-C605-1, Edition 03.2020