Notes 

The actuators must be electrically connected in accordance with local regulations (refer 
to «Connection diagrams»), page 7. 

Regulations and requirements to ensure the safety of people and property must 
be observed at all times! 

The permissible temperatures (refer to «Technical data», page 6) must be observed. 
The connecting cable of the actuator may come into contact with the hot valve body, 
provided the temperature of the valve body does not exceed 80 °C. 

The Mounting Instructions 4 319 0644 0 are enclosed in the product packaging. 
Assembly is made with the union nut; no tools or adjustments are required. The 
actuator must be fitted in position 0 (also refer to «Manual override», page 5) without 
operating voltage. 
In the case of actuators without connecting cable (SSD../00), the separately ordered 
terminal block connector and connecting cable must be fitted. 

90°

43

6

2

Z

01

90°

When commissioning, check wiring and the functioning of the actuator. 

Actuator stem extends   (from position 0 to 1):  Valve opens

Actuator stem retracts   (from position 1 to 0):  Valve closes

During commissioning and whenever 
the operating voltage is switched on, 
the SSD61.. runs a self-calibration 
routine. (Valve stroke

 

0

 

 Max. 

stroke 

 Setpoint). 

Never intervene manually in this 
process. 

Y

Power

ON

100 %

0 %

t

75 s

The second or third attempt at calibration occurs automatically after an 8-minute 
delay.

 

After three failed calibration attempts the actuator stem remains in the extended 
position and the VPI45.. valves are opened. 
For valves with strokes < 1.5 mm, the actuator/valve combination locks after 
three failed calibration attempts. 

Engineering 

 Caution 

Mounting 

Orientation 

Commissioning 

Self-calibration 

 Caution 

Note: Correct 
calibration is only 
possible 

with valve

stroke > 1.5 mm

Summary of Contents for SSD31 Series

Page 1: ...38 78 Смоленск 4812 29 41 54 Сочи 862 225 72 31 Ставрополь 8652 20 65 13 Тверь 4822 63 31 35 Томск 3822 98 41 53 Тула 4872 74 02 29 Тюмень 3452 66 21 18 Ульяновск 8422 24 23 59 Уфа 347 229 48 12 Челябинск 351 202 03 61 Череповец 8202 49 02 64 Ярославль 4852 69 52 93 сайт www acvatix nt rt ru эл почта atv nt rt ru Electrical Actuators for Combi valve types VPI45 SSD31 SSD81 SSD61 SSD31 operating vo...

Page 2: ...Y8L15 Connecting cable 1 5 m ASY8L25 Connecting cable 2 5 m ASY8L25B Connecting cable 2 5 m with Batigyr connector ASY8L45 Connecting cable 4 5 m ASY8L45HF Connecting cable 4 5 m halogen free VDE 0207 24 AC 24 V 3 position ASY98 Retaining screw for terminal block connectors ASY99 Terminal block connector for 3 position actuator SSD81 00 AC 24 V ASY100 Terminal block connector for DC 0 10 V modulat...

Page 3: ...ent switch off in the event of overload and in stroke end positions Parallel operation of 6 SSD31 24 SSD81 and 10 SSD61 possible provided the controllers output is sufficient Terminal block connectors for custom made cables available only for use with AC 24 V and AC DC 24 V actuators Connecting cables with AC 24 V and AC 230 V connectors cannot be mixed up Halogen free cables available 4891Z19 Acc...

Page 4: ... 00 the separately ordered terminal block connector and connecting cable must be fitted 90 4362Z01 90 When commissioning check wiring and the functioning of the actuator Actuator stem extends from position 0 to 1 Valve opens Actuator stem retracts from position 1 to 0 Valve closes During commissioning and whenever the operating voltage is switched on the SSD61 runs a self calibration routine Valve...

Page 5: ...als The actuator must be commissioned only with a correctly mounted valve in place SSD actuators cannot be repaired the complete unit must be replaced Broken connecting cables can be replaced see Accessories page 2 Disposal The device must not be disposed of together with domestic waste This applies in particular to the PCB Legislation may demand special handling of certain components or it may be...

Page 6: ...ts for CE marking EMC directive 2004 108 EC Immunity EN 61000 6 2 Industrial 2 Emission EN 61000 6 3 Residential Low voltage directive 2006 95 EC Electrical safety EN 60730 1 Protection class to EN 60730 II III Contamination level EN 60730 Class 2 Housing protection Upright to horizontal IP40 to EN 60529 UL approbation UL 873 cUL approbation C22 2 No 24 93 Environmental compatibility ISO 14001 Env...

Page 7: ...864Z15 Control signal CLOSE Control signal OPEN System potential AC 24 V G0 Y G 4864Z16 System neutral Control signal DC 0 10 V System potential AC DC 24 V Connection diagrams N Controller Y Actuator L System potential AC 230 V N System neutral Y1 Y2 Control signal OPEN CLOSE 4864A01 L N L N AC 230 V N Y2 Y1 2AF N Y1 Y2 Q1 Q2 Y Q1 Q2 Controller contacts N Controller Y Actuator SP G System potentia...

Page 8: ...кузнецк 3843 20 46 81 Новосибирск 383 227 86 73 Орел 4862 44 53 42 Оренбург 3532 37 68 04 Пенза 8412 22 31 16 Пермь 342 205 81 47 Ростов на Дону 863 308 18 15 Рязань 4912 46 61 64 Самара 846 206 03 16 Санкт Петербург 812 309 46 40 Саратов 845 249 38 78 Смоленск 4812 29 41 54 Сочи 862 225 72 31 Ставрополь 8652 20 65 13 Тверь 4822 63 31 35 Томск 3822 98 41 53 Тула 4872 74 02 29 Тюмень 3452 66 21 18 ...

Reviews: