Document No. 129-253
Installation Instructions
August 2, 2007
Page 2 of 4
Siemens Building Technologies, Inc.
Installation
If you are mounting an actuator on a new valve, begin with
the instructions
Mounting an Actuator on a Valve.
Removing the actuator from a valve
1.
Remove the terminal cover (Figure 2) using a Phillips
head screwdriver,
2.
Identify and disconnect wiring from the terminals.
3.
Remove wiring retention screw.
4.
Do one of the following:
•
Remove plenum cable adapter and plenum
cable;
or
•
Remove flex conduit.
5.
Loosen the actuator coupling on the valve (Figure 3,
reverse #2).
6.
Remove the actuator from the valve.
EA1154R1
WIRING TERMINAL
WITH REMOVABLE
TERMINAL BLOCK
TERMINAL
COVER
AND SCREWS
FLEX
CONDUIT
ADAPTER
PLENUM CABLE
ADAPTER
(OPTIONAL USE)
WIRING
RETENTION
SCREW
Figure 2. SSC Actuator Components.
Mounting an Actuator on a Valve
1.
If you are attaching the actuator to a new valve,
remove the protective plastic cap from the valve
stem.
2.
Turn the manual position indicator on the top of the
actuator to the 0 position (Figure 10).
3.
Using a Phillips head screwdriver, remove the
terminal cover (Figure 2).
4.
Remove wiring retention screw.
5.
Remove plenum cable adapter.
6.
For plenum applications, complete wiring as follows:
a.
Route cable through plenum cable adapter so
there is sufficient cable to complete wiring
terminations.
b.
Insert plenum cable adapter into flex conduit
adapter and secure in place with wiring retention
screw.
NOTE:
Insert wiring retention screw in hole farthest from
wiring terminals. (The hole nearest the wiring
terminals is to secure the terminal cover in
place.)
c.
Continue with Step 8.
7.
For 3/8-inch flex conduit applications, complete
wiring as follows:
a.
Discard plenum cable adapter.
b.
Insert flex conduit into flex conduit adapter and
secure in place with wiring retention screw.
NOTE:
Insert wiring retention screw in hole
farthest from wiring terminals. (The
hole nearest the wiring terminals is
to secure the terminal cover in
place.)
c.
Route wiring through flex conduit for wiring
terminations.
8.
Connect wires to wiring terminals per the
Wiring
section of this document.
9.
Secure the terminal cover in place over the wiring
terminals (Figure 2) using a Phillips head
screwdriver,
10. Place the actuator on the valve and firmly hand-
tighten (Figure 3).
CAUTION:
Hand-tighten the actuator to the valve. The
use of tools to tighten the assembly together,
will cause damage.
The installation is complete.
EA1160R1
1
2
Figure 3. Coupling Actuator to Valve.
Manual Override
To position the actuator manually, use the manual override
knob in the center of the position indicator (Figure 4).
CLOCKWISE
EXTENDS
SHAFT
COUNTER
CLOCKWISE
RETRACTS
SHAFT
EA1161R1
A
B
A
B
Figure 4. Manual Override.