Installation 

If you are mounting an actuator on a new valve, begin with 
the instructions 

Mounting an Actuator on a Valve.

 

Removing the actuator from a valve 

1. 

Remove the terminal cover (Figure 2) using a Phillips 
head screwdriver,  

2. 

Identify and disconnect wiring from the terminals.  

3. 

Remove wiring retention screw.  

4. 

Do one of the following: 

 

Remove plenum cable adapter and plenum 
cable; 

or

 

 

Remove flex conduit.  

5. 

Loosen the actuator coupling on the valve (Figure 3, 
reverse #2).  

6. 

Remove the actuator from the valve. 

EA1154R1

WIRING TERMINAL

WITH  REMOVABLE

TERMINAL BLOCK

TERMINAL

COVER

AND SCREWS

FLEX

CONDUIT

ADAPTER

PLENUM CABLE

ADAPTER

(OPTIONAL USE)

WIRING

RETENTION

SCREW

 

Figure 2.  SSC Actuator Components.  

Mounting an Actuator on a Valve 

1. 

If you are attaching the actuator to a new valve, 
remove the protective plastic cap from the valve 
stem.  

2. 

Turn the manual position indicator on the top of the 
actuator to the 0 position (Figure 10).  

3. 

Using a Phillips head screwdriver, remove the 
terminal cover (Figure 2).

 

 

4. 

Remove wiring retention screw.  

5. 

Remove plenum cable adapter.  

6. 

For plenum applications, complete wiring as follows: 

a. 

Route cable through plenum cable adapter so 
there is sufficient cable to complete wiring 
terminations.  

b. 

Insert plenum cable adapter into flex conduit 
adapter and secure in place with wiring retention 
screw. 

NOTE: 

Insert wiring retention screw in hole farthest from 
wiring terminals. (The hole nearest the wiring 
terminals is to secure the terminal cover in 
place.)  

c. 

Continue with Step 8.  

 

7. 

For 3/8-inch flex conduit applications, complete 
wiring as follows: 

a. 

Discard plenum cable adapter.  

b. 

Insert flex conduit into flex conduit adapter and 
secure in place with wiring retention screw.  

NOTE: 

Insert wiring retention screw in hole 
farthest from wiring terminals. (The 
hole nearest the wiring terminals is 
to secure the terminal cover in 
place.)  

c. 

Route wiring through flex conduit for wiring 
terminations. 

8. 

Connect wires to wiring terminals per the 

Wiring

 

section of this document.  

9. 

Secure the terminal cover in place over the wiring 
terminals (Figure 2) using a Phillips head 
screwdriver,  

10.  Place the actuator on the valve and firmly hand-

tighten (Figure 3).  

 

 

CAUTION:

 

 

Hand-tighten the actuator to the valve. The 
use of tools to tighten the assembly together, 
will cause damage. 

 
The installation is complete. 

EA1160R1

1

2

 

Figure 3.  Coupling Actuator to Valve.  

 

Manual Override  

To position the actuator manually, use the manual override 
knob in the center of the position indicator (Figure 4).  

CLOCKWISE

EXTENDS

SHAFT

COUNTER

CLOCKWISE

RETRACTS

SHAFT

EA1161R1

A

B

A

B

  

Figure 4.  Manual Override. 

Summary of Contents for SSC61.5U

Page 1: ...er Small flat blade screwdriver Wire stripper Prerequisites WARNING 1 If mounting the actuator to a valve already in line either close the shut off in the piping upstream first then downstream or switch off the pump to allow the differential pressure in the valve to drop 2 Disconnect the controller power before replacing the actuator 3 If high voltage cable is co located with the SSC actuator cond...

Page 2: ... plenum cable adapter so there is sufficient cable to complete wiring terminations b Insert plenum cable adapter into flex conduit adapter and secure in place with wiring retention screw NOTE Insert wiring retention screw in hole farthest from wiring terminals The hole nearest the wiring terminals is to secure the terminal cover in place c Continue with Step 8 7 For 3 8 inch flex conduit applicati...

Page 3: ...sformer is 100 VA Do not power more than 10 actuators with one transformer NEUT CONTROLLER ACTUATOR EARTH GROUND ISOLATING CLASS 2 TRANSFORMER FOR 24 Vac POWER 120 Vac 1 0 Y2 Y1 G 24 Vac EA0795R1 Y2 Retracts actuator shaft Y1 Extends actuator shaft G System potential Figure 6 SSC81U NSR Floating Control EA1235R1 NEUT CONTROLLER EARTH GROUND ISOLATING CLASS 2 24 Vac TRANSFORMER 120 Vac 24 Vac ACTUA...

Page 4: ...sition indicator Figure 10 Position Indicator Output Shaft 0 Retracted 1 Extended NOTE 0 and 1 markings are intended for reference only and not stroke measurement 0 1 EA1158R1 Figure 10 Position Indicator Shown in 0 Position Troubleshooting Check the wiring for the proper connections References Technical Instructions Document No EA 599 15 Powermite 599 Series SSC Electronic Valve Actuator 24 Vac P...