Siemens Building Technologies 

Electrical Actuators 

CA1N4895en 

HVAC Products 

 

08.03.2004 

When first connected to power, or 
after a power failure, the capacitor 
which stores energy for the fail-safe 
function will be charged. This process 
takes up to 180 seconds. While the 
capacitor is being charged, the 
actuator cannot respond to any Y 
control signals. 

max 180 s

max
30 s

Charging

Calibration

Discharge

48

95Z01

en

Stroke 

[

%

]

100

0

t

60 s

Normal
actuator
operation

 

On completion of the charging process and auto calibration (see below), the "Open" 
and "Close" travel are proportional to the DC 0…10 V control signal. 
In the event of a power failure of more than 5 seconds, the actuator will return 
mechanically to its 0 % stroke position within 30 seconds, closing the valve 
(A 

 AB). 

 

When the AC / DC 24 V supply is applied for the first time, the actuators calibrate 
themselves independent of the control signal. In this process, the actuator drives the 
valve to the mechanical end stops and stores the associated positions permanently in the 
form of electronic values. The positioning signal is only active on completion of this 
calibration process. Calibration takes about 60 seconds. 
The SSC61.5 only performs auto calibration when the charging process of 180 seconds  
is completed. 
 
If the calibrated actuator is used with 
some other valve (e.g. a replacement 
valve), it must be recalibrated. For that 
purpose, the PCB beneath the terminal 
cover has a slot (see illustration). To 
make the recalibration, use a 
screwdriver and connect the 2 contacts 
behind the slot for about 1 second. 

3

2

1

48

95

Z

02

 

 

The calibration can only be made correctly if the actuator is fitted to a valve (refer to 
«Equipment combinations»). 
 

• 

Plastic cover 

• 

Locking-proof, maintenance-free gear train 

• 

Manual adjustment with rotary knob 

• 

Reduced power consumption in the holding positions 

• 

Load-dependent switch-off in the event of overload and in stroke limit positions 

Accessories 

 

Type ASK30 

Electrical fail-safe 
function 

SSC61.5

 

Auto calibration 

SSC61 and SSC61.5

 

Recalibration 

 

Features and benefits 

Mounting kit 

Summary of Contents for SSC31

Page 1: ...n Nominal force 300 N Automatic identification of valve stroke Direct mounting with coupling nut no tools required Cable connection via screw terminals Manual override indication of position and direction of travel Parallel connection of multiple actuators Special UL listed versions Use For operation of Siemens valves of the VVP45 VXP45 and VMP45 range for water side control of hot water and cooli...

Page 2: ...ombinations Type reference Type of valve kvs m 3 h PN class Data Sheet VVP45 2 port valves 0 25 25 PN16 N4845 VXP45 3 port valves VMP45 3 port valves with T bypass 0 25 4 VVG45 1 2 port valves 0 63 25 VXG45 1 3 port valves X3i 1 3 port valves 0 7 14 Retrofitting to former L G valves 1 With ASK30 mounting kit Function mechanical design When the actuator is driven by a 3 position or DC 0 10 V contro...

Page 3: ...ves the valve to the mechanical end stops and stores the associated positions permanently in the form of electronic values The positioning signal is only active on completion of this calibration process Calibration takes about 60 seconds The SSC61 5 only performs auto calibration when the charging process of 180 seconds is completed If the calibrated actuator is used with some other valve e g a re...

Page 4: ... of the SSC always check to ensure that the actuator concerned is mounted on a valve refer to Equipment combinations Calibrating the SSC61 or SSC61 5 without a valve connected causes the actuator to lock in position 1 To recalibrate after mounting on a valve disconnect power and reset the stroke manually from position 1 to 0 refer to Recalibration The rotary knob can be used to drive the actuator ...

Page 5: ... Products Technical data SSC31 SSC81 SSC61 SSC61 5 AC 24 V or DC 24 V Power supply Rated voltage Voltage tolerance AC 230 V 15 AC 24 V 20 20 25 Rated frequency 50 60 Hz Max power consumption 6 VA 0 8 VA 2 VA 2 VA 1 Fuse for incoming cable fast 2 A Control Control signal 3 position DC 0 10 V Input impedance for DC 0 10 V 100 kOhm Positioning accuracy for DC 0 10 V 2 of nominal stroke Parallel opera...

Page 6: ...utput is sufficient General ambient conditions Operation IEC 721 3 3 Transport IEC 721 3 2 Storage IEC 721 3 1 Environmental conditions class 3K3 class 2K3 class 1K3 Temperature 5 50 C 25 70 C 25 70 C Humidity 5 95 r h 95 r h 5 95 r h Connection terminals All actuators must be electrically connected and installed in accordance with local safety regulations Y2 Y1 N 4895Z06 Control signal CLOSE AC 2...

Page 7: ...l 4864A01 L N L N AC 230 V N Y2 Y1 2AF N Y1 Y2 Q1 Q2 Y Q1 Q2 Controller contacts N Controller Y Actuator SP System potential AC 24 V SN System neutral 4864A02 Y1 G G0 SP SN AC 24 V G Y2 Y1 Y2 N Q1 Q2 2AF Y Q1 Q2 Controller contacts N Controller Y Actuator SP System potential AC 24 V 4864A03 Y N Y G0 G Y G0 SP SN AC 24 V DC 24 V G 2AF SN System neutral SSC31 SSC81 SSC61 SSC61 5 ...

Page 8: ...ns Building Technologies Electrical Actuators CA1N4895en HVAC Products 08 03 2004 Dimensions All dimensions in mm 48 110 8 89 2 21 6 115 1 132 5 4895Z08 G 2004 Siemens Building Technologies AG Subject to change ...

Reviews: