Wiring the SRC-8
WIRING
(Refer to Figure 4)
Refer to Figure 4 below to wire the SRC-8 into
the SXL-EX System.
The wiring for the Form C relay circuits from
terminal blocks 1-8 is also shown in Figure 4.
For information on programming the relays on
the SRC-8, refer to the
SXL-EX Manual,
P/N
315-095997.
BATTERY CALCULATIONS
Battery backup is required for the SRC-8. To
determine the size battery you need, use the
battery calculation table in the
SXL-EX Manual,
P/N 315-095997.
Notes:
1. The SXL-EX Control Panel meets NFPA 72 Local System requirements.
2. All wiring must be in accordance with NFPA 70.
3. Form C relay contacts are shown de-energized. They are suitable for resistive load only.
4. Refer to the
Battery Calculations
in the manual to determine battery needs.
5. Minimum 18AWG wire to all field connections.
C
C
N
C
N
O
C
C
N
C
N
O
C
C
N
C
N
O
C
C
N
C
N
O
C
C
N
C
N
O
C
C
N
C
N
O
C
C
N
C
N
O
C
C
N
C
N
O
RELAY
TB1
RELAY
TB2
RELAY
TB3
RELAY
TB4
RELAY
TB5
RELAY
TB6
RELAY
TB7
RELAY
TB8
FORM C
RELAY 1
FORM C
RELAY 2
FORM C
RELAY 3
FORM C
RELAY 4
FORM C
RELAY 5
FORM C
RELAY 6
FORM C
RELAY 7
FORM C
RELAY 8
TO SXL-EX
MAIN BOARD
TB-3
STYLE 4
SUPERVISED
-V
+24V
DATA
EARTH
+24V
DATA
-V
ER
TB9
SRC-8
DS1
POLL
PROGRAMMABLE
POSITIVE AND NEGATIVE
GROUND FAULT DETECTED
AT <20K FOR TERMINALS ON TB9
Electrical Characteristics
Supervisory: 18 mA
Alarm: 26mA per relay
Electrical Characteristics
of Form C Relays
2A at 30 VDC and 120 VAC
resistive only