P/N 315-087691-11
Typical Wiring
NOTES
1. Relay contacts are shown de-energized.
2. Arrange P1 through P8 for either a high going input (position A) or a low going signal (position B) for the related relay.
3. Relay 1K1 is shown in position A for high going actuation; the input may come from terminal 1 or 7 of CP-35 or from terminal 1 or 7 of ZU-35.
4. Relay 2K1 is shown in position B for low going actuation; it may be returned to terminal 36 of SR-35 device.
5. Relay contacts are rated 2A, 30 VDC/125 VAC.
6. Minimum wire size: 18 AWG
Maximum wire size: 12 AWG
7. The SR-35 is non-power limited on all terminals.