background image

 

 

Installation Instructions

Document No. 129-399

January 18, 2008

 

SQM5… Reversing Actuator with Line Voltage Input Signal 

 

 

Item Number 129-399, Rev. BA

 

Page 1 of 4 

Product Description 

Reversing actuator used to position flow control 
valves, butterfly valves, dampers, or any application 
requiring rotary motion with line voltage input signal 
for Position Proportioning or Floating Control. 

Product Numbers 

SQM5x.xxxRx

A

x  for line voltage input signals 

Actuator Torque: 

SQM50.2…    90 in/lb 

SQM50.3…    90 in/lb 

SQM50.4…    140 in/lb 

SQM53.4…    200 in/lb 

SQM56.5…    310 in/lb 

SQM56.6…    400 in/lb 

Max Shaft Torque: 

AGA58.1    200 in/lb 

AGA58.3    220 in/lb 

AGA58.4    270 in/lb 

AGA58.7    400 in/lb 

SQM… motors allow torque on either end of the 
AGA58.3 and AGA58.4 shafts. 

NOTE: 

  For detailed information, see Technical 

Instructions 155-517P25. 

Caution Notation 

CAUTION:  

 

Equipment damage may 
occur if procedures are not 
followed as specified. 

Installation

 

Cover Removal 

Use a Phillips screwdriver to loosen the two screws 
on the actuator cover corners. See Figure 1. 

Lift the screws and raise the cover. See Figure 2. 

 

EA0564R1

   

EA0568R1

 

 

Figure 1. 

Figure 2. 

Rotational Direction Verification 

Actuator model numbers that end with “R” are 
factory configured for clockwise (cw), minimum to 
maximum rotation when facing the gear end of the 
actuator, or counterclockwise (ccw) rotation when 
facing the other end of the actuator. The gear end of 
the actuator is the side opposite of the visual 
position indicator 

Actuator Mounting 

SQM5… actuators can be mounted in any 
orientation. Optional base mounting brackets are 
available. 
 
SQM5… actuators can also be face-mounted using 
self-tapping screws in combination with the various 
holes on the face of the actuator gear end. 

Switch Adjustment 

SQM5…actuators are factory-wired with Switch I 
(maximum), Switch II (fully closed/economy position) 
and Switch III (minimum/low-fire). The individual 
switch cams I, II, and III are factory set to 90

°

, 0

°

 

and 10

°

, respectively. See Figures 3 and 4. 

Summary of Contents for sqm50

Page 1: ...lowed as specified Installation Cover Removal Use a Phillips screwdriver to loosen the two screws on the actuator cover corners See Figure 1 Lift the screws and raise the cover See Figure 2 EA0564R1 EA0568R1 Figure 1 Figure 2 Rotational Direction Verification Actuator model numbers that end with R are factory configured for clockwise cw minimum to maximum rotation when facing the gear end of the a...

Page 2: ...A3 actuators have a 90 potentiometer and the switches must be adjusted between 0 and 90 SQM5x xxxRxA4 actuators have a 135 potentiometer and the switches must be adjusted between 0 and 135 Shaft Adjustment The actuator shaft can be disengaged by pressing the silver shaft release button The button is located above the grounding screw under the hinged terminal protection cover and to the right of th...

Page 3: ...54R3 Figure 5 AGA56 1A97 Terminal and Auto Manual Board Commissioning Manual Operation 1 Set the AUTO MAN switch in the MAN position 2 Connect ground to the screw located below the shaft release button 3 Connect neutral to the double terminal block located on the left side of the gray switch housing 4 Only terminal L must be powered to enable manual operation The actuator can now be driven to the ...

Page 4: ...4 6 1 3 16 30 2 1 16 52 5 2 1 16 52 5 1 7 16 36 EA0522R2 5 1 4 133 7 1 16 180 2 1 16 52 5 2 1 16 52 5 3 8 10 Pg 13 5 1 2 NPSM M6 7 1 16 180 5 16 8 5 6 7 16 164 5 16 7 5 1 16 1 1 8 3 5 EA0542R3 4 7 16 113 3 1 8 80 5 3 16 132 M6 Figure 8 SQM5x xxxRxx Dimensions in Inches Millimeters Information in this publication is based on current specifications The company reserves the right to make changes in s...

Reviews: