Installation
4
The transmitter is secured to a 35 mm DIN rail to DIN EN 60715.
Comply with the ambient conditions specified in the technical data.
WARNING
Hazardous areas
Gas hazardous area:
– The enclosure has IP20 degree of protection. With an intrinsically-safe power supply,
you can therefore assemble the intrinsically-safe device versions without an
additional enclosure.
– For ic and nA modes, use a suitable protective enclosure / terminal box which
satisfies at least IP54 degree of protection.
Dust hazardous zone:
For use in a dust hazardous zone, install in a suitable metal protective enclosure /
terminal box which satisfies at least IP6X degree of protection.
CAUTION
Electromagnetic Compatibility
If the sensor is installed outside a closed building, you must check the transmitter for
correct functioning following a lightning stroke.