Factory setting Pt100 (DIN IEC)
In three-wire input
Pickup offset
0 °C (0 °F)
Damping
0.0 s
Certificates and approvals
Explosion protection ATEX and further approval authorities
ATEX PTB 05 ATEX 2049 X
Only the technical specifications listed in the certificates apply to applications in potentially explosive
atmospheres.
"Gas intrinsic safety" protec‐
tion type
II 1 G Ex ia IIC T6/T4 Ga
II (1) 2 G Ex ib [ia Ga] IIC T6/T4 Gb
II (1) 3 G Ex ic [ia Ga] IIC T6/T4 Gc
II 3 G Ex ic IIC T6/T4 Gc
"Non-sparking" protection
type
II 3 G Ex nA IIC T6/T4 Gc
II 3 G Ex nA[ic] IIC T6/T4 Gc
"Dust intrinsic safety" pro‐
tection type
II 1 D Ex ia IIIC T115°C Da
Explosion protection FM for USA
FM 3024169C
Electrical data, operating conditions and installation instructions for operation in hazardous areas
can be found in the FM Certificate of Compliance as well as in the associated Control Drawing
A5E03638596A.
IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6
Cl I, ZN 0 AEx ia IIC T4/T5/T6
NI, S Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6
NI IIC T4/T5/T6
Protection against explosion according to FM for Canada (cFMus)
FM 3024169
Electrical data, operating conditions and installation instructions for operation in hazardous areas
can be found in the FM Certificate of Compliance as well as in the associated Control Drawing
A5E03638596A.
IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6
Cl I, ZN 0 Ex ia IIC T4/T5/T6
NI, S Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6
NI IIC T4/T5/T6
Technical data
12.1 SITRANS TH100
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB
195