SITRANS TH200/TH300
Operating Instructions, 06/2010, A5E00393069-03
71
Technical data
11
11.1
Technical data
Input point
Resistance thermometer input point
Measured variable
Temperature
Sensor type
According to IEC 60751
Pt25 ... Pt1000
According to JIS C 1604; a=0.00392
K
-1
Pt25 ... Pt1000
According to IEC 60751
Ni25 ... Ni1000
Special type
Via special characteristic curve (max. 30 points)
Sensor factor
0.25 ... 10 (adaptation of the basic type, e.g. Pt100, to
version Pt25 ... Pt1000)
Units of measurement
°C or °F
Interface
Standard connection
1 resistance thermometer (RTD) in two-wire, three-wire
or four-wire input
Averaging
2 equal resistance thermometers in two-wire input for
averaging the temperature
Differentiation
2 equal resistance thermometers (RTD) in two-wire input
(RTD 1 - RTD 2 or RTD 2 - RTD 1)
Connection
Two-wire input
Line resistance can be assigned in the parameters
≤100 Ω (loop resistance)
Three-wire input
No trim necessary
1)
Four-wire input
No trim necessary
Sensor current
≤ 0.45 mA
Measuring cycle
≤ 250 ms for 1 sensor with break monitoring
Break monitoring
Always active (cannot be switched off)
Short circuit monitoring
Can be switched on/off (default value = ON)
Measuring range
Can be set in the parameters (see table in chapter Digital
Min. measuring span
10 °C (18 °F)
Characteristic curve
Linear to temperature or special characteristic curve
1)
Prerequisites: same resistance for all three lines.