Functions
9.16 Factory parameters
SITRANS TH200/TH300
58
Operating Instructions, 06/2010, A5E00393069-03
The following pair of values must be transferred to the parameter assignment software for
the characteristic curve correction of the pair of values i = 3: X[3] = 20 % and Y[3] = 20 %.
9.16
Factory parameters
Using the menu command Device ➜ Factory trim ➜ Reset factory settings, the configuration
of the transmitter is reset to its default values.
Note
Factory reset
The menu command Device ➜ Factory trim ➜ Reset factory settings always resets the
parameters of the transmitter to the default values in the table listed below.
This factory reset has the same effect for "devices supplied ex stock" or "devices set
customer-specifically".
Furthermore, resetting the transmitter to its default values also resets a customer-specific
digital-to-analog converter trim and sensor calibration (one point trim or two point trim).
Once a factory reset has been performed, the transmitter has the following configuration:
Parameter
Reset to value
DAY
Is not reset
Description
Is not reset
Message
Is not reset
Serial number
Is not reset
Installation date (electronics)
Is not reset
Sensor class
Resistance thermometer
Sensor type
Pt100 DIN IEC 751
Interface
Standard connection
Sensor connection
Three-wire input
Sensor factor
1.00
Sensor offset 1
0.00 °C
Start of scale value
0 °C
Full scale value
100 °C
Unit
°C
Break monitoring
ON
Short circuit monitoring
ON
Short circuit limit
10 Ω
Lower end point analog output
Is not reset
Upper end point analog output
Is not reset
Alarm value
Is not reset
Linearization type
Linear to temperature
Attenuation
0.00 s
Runtime meters PV
Are all reset to 0 h