Icons
Selection of the block icon in CFC
Special features
1
-
Block icon in the "Out of service"
operating mode
The display formats (e.g. decimal places) for the 4 to 20 mA signal and the four HART variables
are specified in the AnalogValueFormat1..4 properties of the block icon.
For more information on the block icon and operating options in the block icon, refer to the
following sections in the APL online help:
● "Configuring the block icons"
● "Block icon structure"
● "Operation via the block icon"
6.2
PLut400
6.2.1
Description of PLut400
Function
The PLut400 block is the interface to the operator panel for the technological block Lut400.
It is a message-capable block and generates the same Alarm_DQ messages as the associated
technological block.
Configuration notes
The BlockConnector input of the PLut400 must be interconnected to any desired Lut400 output.
So the data that are important for the block (as information about states or messages) are
automatically analyzed and displayed by the panel block.
Note
The
ENO
output must not be used for interconnection with the
BlockConnector
input.
Calling OBs
This is the cyclic interrupt OB in which you install the block (e.g. OB32). Additionally in the
OB100 (see startup characteristics).
SITRANS LUT400
6.2 PLut400
SITRANS Library for PCS 7
182
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...