The FbMag6T block contains a template for process tag types in the SITRANS Library as an
example.
Example of a process tag type: Template of Mag6T
Startup characteristics
● FbMag6T sets bit 16#xx01xxxx of the Mode input to signal a restart.
● The module ID is read from the addressed DP Slave and verified for consistency with that
of MAG6000. Output QModF (module error) is set if the result is negative.
● OB100 transfers the following values to the module if the corresponding modules are
configured in HW Config:
- Reset the totalizer (SET_TOT): 16#00 (no Reset)
- Command of totalizers (MODE_TOT): 16#04 (invalid command to prevent changes of the
totalizer states)
- Dosing commands (DCtr): 16#00 (no enable, no command)
Status word allocation for
Status
parameter
This block does not have the
Status
parameter.
5.3.2
Operating modes for FbMag6T
This block does not have any operating modes.
5.3.3
Functions of FbMag6T
The functions for this block are listed below.
Read cyclic values from process image
The process values are read from the process image (partition) at each block call and then
written, including their signal states, to output structure CyclData.Input as well as to the
outputs
VolFlow, Tot1VF
and
Tot2VF
. The values are addressed via input
structure
Addr
, with -1 indicating that the corresponding value was not configured in HW
Config.
SITRANS F M MAG 6000
5.3 FbMag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
141