SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
36
A5E03434626-04, 05/2015
6.5
Disposal
Devices identified by this symbol may not be disposed of in the municipal waste
disposal services under observance of the Directive 2002/96/EC on waste electronic
and electrical equipment (WEEE).
They can be returned to the supplier within the EC or to a locally approved disposal
service. Observe the specific regulations valid in your country.
Note
Special disposal required
The device includes components that require special disposal.
•
Dispose of the device properly and environmentally through a local waste disposal contractor.
7
Technical specifications
7.1
Overview of technical data
Introduction
The following overview of technical data provides you with a quick and easy access to relevant data and characteristic
numbers.
Remember that tables in part contain the data of the three communication types HART, PROFIBUS and
FOUNDATION
TM
Fieldbus. This data deviates in many cases. Therefore, adhere to the communication type used by you
when using the technical data.
Contents of the chapter
●
SITRANS P DS III input (Page 36)
●
SITRANS P410 input (Page 42)
●
●
Operating conditions (Page 44)
●
Construction (Page 47)
●
Display, keyboard and auxiliary power (Page 51)
●
Certificates and approvals (Page 52)
7.2
SITRANS P DS III input
Gauge pressure input
Measured variable
Gauge pressure
Span continuously adjustable) or measuring
range, max. operating pressure (in
accordance with 97/23/EC Pressure
Equipment Directive) and max. test
pressure (in accordance with DIN 16086)
(for oxygen measurement, max. 100 bar
and 60 °C ambient temperature/process
temperature)
Span
1)
Maximum operating
pressure MAWP (PS)
Maximum test pressure
8.3 … 250 mbar
0.83 ... 25 kPa
0.12 … 3.6 psi
4 bar
400 kPa
58 psi
6 bar
0.6 MPa
87 psi
0.01 … 1 bar
1 ... 100 kPa
0.15 … 14.5 psi
4 bar
400 kPa
58 psi
6 bar
0.6 MPa
87 psi