SITRANS LVL200S - Operating Instructions
33837-EN-161128
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
In the basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³)
can be detected. For products with lower density, you have to set the
switch to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
•
Control lamp for indication of the switching condition (1)
•
DIL switch for mode adjustment - A/B (2)
•
DIL switch for sensitivity adjustment (3)
Note:
Always immerse the tuning fork of SITRANS LVL200S in a liquid to
test its function. Do not test the function of SITRANS LVL200S with
your hand. This can damage the sensor.
6.2 Adjustment elements
1
2
3
4
1
2
3
Fig. 11: Oscillator SWE60T - Transistor output
1 Control lamp (LED)
2 DIL switch for mode adjustment
3 DIL switch for sensitivity adjustment
Control lamp for indication of the switching status
•
Green = Output closed
•
Red = Output open
•
red (flashing) = failure
With the mode adjustment (A/B) you can change the switching
condition of the relay. You can set the required mode according to the
"
Function table
" (A - max. detection or overflow protection, B - min.
detection or dry run protection).
Function/Configuration
Signal lamp (1)
Mode adjustment (2)
Siemens Controls