Diagnostics and troubleshooting
9.5 Treatment of measurement errors
Fault description
Cause
Rectification
into overfill protection mode. The
max. level (0 m distance) as well
as the status message "
Overfill
protection
are output.
Remove contamination on the
antenna
Fault description
Cause
Rectification
Measured value remains
unchanged in the close
range during emptying
False signal larger than the level
echo
Level echo too small
Check measuring point: Antenna
should protrude out of the threaded
mounting nozzle, possible false
echoes through flange nozzle?
Remove contamination on the
antenna
In case of interferences due to
installations in the close range:
Change polarisation direction
After eliminating the false signals,
the auto false echo suppression
must be deleted. Carry out a new
auto false echo suppression
Measured value jumps
sporadically towards
100 % during emptying
Varying condensation or
contamination on the antenna
Carry out auto false echo
suppression or increase auto false
echo suppression in the close range
by editing
Fault description
Cause
Rectification
Min./max. adjustment not correct
Adapt min./max. adjustment
Measured value shows a
too low or too high level
Incorrect linearization curve
Adapt linearization curve
Due to the process, the amplitude
of the product echo decreases
A auto false echo suppression was
not carried out
Carry out a auto false echo
suppression
Measured value jumps
towards 100 %
Amplitude or position of a
false signal has changed (e.g.
condensation, buildup); auto
Determine the reason for the
changed false signals, carry out
36
SITRANS LR140
Operating Instructions, 08/2020,
A5E50352144