Ambient conditions
11
Basic units
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
UPS module
6EP4197-8AB00-0XY0
Expansion modules
6EP4436-8XB00-0CY0
6EP4437-8XB00-0CY0
6EP4436-8XB00-0DY0
Buffer modules
6EP4297-8HB00-0XY0
6EP4297-8HB10-0XY0
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
Ambient temperature
-25 ... 60 °C for natural convection (self convection)
Tested according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 humid heat, constant
•
EN 60068-2-14 temperature change
Transport and storage tem-
perature
-40 ... 85 °C
Tests (packed for shipping) according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 humid heat, cyclic
-40 … 70 °C
Humidity class
Climate class 3K3 according to EN 60721; further, maximum relative humidity 95 %, how-
ever no condensation
Mechanical stressing during
operation
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 – 8.4 Hz
2 g acceleration in the range 8.4 – 150 Hz
•
EN 60068-2-27 shock, test Ea:
Acceleration 150 m/s
2