Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
282
Manual, 09.2018, A5E36758446-5-76
The following data can be seen for every output available in the system:
Submenu
Data
PSU8600 / CNX8600
Output [n]
Operating state
switched off/switched on
Output voltage
[V]
Setpoint output voltage
[V]
Maximum output current
[A]
Output current
[A]
Set response threshold
[A]
7.7.6.4
Online functions
The procedure to use the online functions of the web server is described below.
Note
With the exception of the firmware update function, all online functions for the existing
PROFINET connection are inhibited.
Output ON/OFF
Using the "Output ON/OFF" function you can switch on the outputs again after an automatic
shutdown. Outputs that were switched off manually or using the remote configuration are not
switched on using the "Output ON/OFF" function.