Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
263
Data
Description
Data type
9 = FWUpdate
A firmware update is
presently being per-
formed.
The basic unit generates
the signal.
10 = Buffer End
End of buffering
Charging state
(0-100 %)
Charge state of the buffer module
Unsigned8
Buffer disabled by
input (0/255)
Buffer component was deactivated via the control contact.
Unsigned8
Fill byte(s)
-
Unsigned8
LED color
Actual LED color. Each
LED is represented by 2
bits:
•
Bit0/1: OK
•
Bit2-15: unused = 0
0
LED is off.
Unsigned16
1
LED lit green.
2
LED lit red.
3
LED lit yellow.
LED state
Actual display status of
the LEDs. Each LED is
represented by 2 bits:
•
Bit0/1: OK
•
Bit2-15: unused = 0
0
LED is off.
Unsigned16
1
LED lights up.
2
LED flashes at 1 Hz.
3
LED flashes at 2 Hz
7.6.2.5
Data sets SITOP UPS8600
Index 1: General (reading/writing)
Data
Description
Data type
Maximum charging
power
Maximum charging power 0 = Off
Module is not charged
Unsigned8
1 = Low
60 W charging power
2 = High (default set-
ting)
120 W charging power
Battery test interval
Battery test interval
0 = Off
The battery module is not
tested.
Unsigned8
1 … 24
Default setting: 6
The connected battery
modules are tested every
n hours.
Buffer Timer Enable
(0/255)
Specifies whether the timer is activated
Unsigned8
Fill byte(s)
-
Unsigned8
Buffer timer [ms]
Settings for the buffer timer
Unsigned32