Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
238
Manual, 09.2018, A5E36758446-5-76
7.6.2
Reading and writing data sets
7.6.2.1
Overview of reading and writing data sets
An overview of all of the data sets, which are communicated between the power supply
system and PROFINET IO-Controller, is listed in the following tables. Here, a distinction is
made between the following data sets:
●
Reading data sets: Data that is sent from the SITOP PSU8600, expansion modules, the
buffer modules and the UPS modules to the PROFINET IO-Controller .
●
Writing data sets: Data that is sent from the PROFINET IO-Controller to the
SITOP PSU8600, the expansion modules, the buffer modules and the UPS modules.
Additional information about the individual data sets is provided in the corresponding
subchapters.
You can find information about the write behavior SITOP PSU8600 in mode STOP or RUN in
Section "Parameter write behavior of the SITOP PSU8600 (Page 348)".
Reading and writing data sets SITOP PSU8600
Index
Slot
Subslot Data set
Type
Description
Data size
1
0
1
General remote values Reading
General settings of
the SITOP PSU8600.
10 bytes
Writing
Adjustable parameters for generally
configuring the SITOP PSU8600.
10 bytes
1
0
3
Output1 remote target
values
Reading
Configuring output 1 of the
SITOP PSU8600.
10 bytes
Writing
Adjustable parameters for output 1 of
the SITOP PSU8600.
10 bytes
6
0
1
Device information
Reading
Information about the SITOP PSU8600. 42 bytes
7
0
1
Hardware settings
Reading
Hardware settings of
the SITOP PSU8600 (settings that were
made at the front of the device).
60 bytes
8
0
1
Buffer handling values Reading
Configuring the buffer behavior.
24 bytes
Writing
Adjustable parameters for the buffer
behavior.
24 bytes
16
0
1
SITOP command
interface
Writing
Function interface to execute special
functions not covered by the configura-
tion software or not able to be accessed
6 bytes
Result of SITOP com-
mand interface
Reading
Status of processing the requested
function call of the "SITOP command
interfaces"
4 bytes
32
0
1
State information
Reading
Status information about
the SITOP PSU8600.
32 bytes
33
0
1
Actual buffer state
information
Reading
Status information about the buffer
properties.
12 bytes
48
0
1
PROFIenergy values
Reading
PROFIenergy settings of
the SITOP PSU8600.
36 bytes