Description, device design, dimension drawing
2.6 Remote contact
SITOP PSU8200 1ph
18
Manual, 11.2014, C98130-A7633-A1-3-7629
2.6
Remote contact
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Remote contacts (15, 16)
⑤
Non-isolated input for remote ON/OFF switching of the power supply.
Function: The device is remotely switched off when contacts 15, 16 are short-circuited
(R < 8
kΩ). If the power supply is shut down and latched in the "latching shutdown" mode
as a result of an overload, then it can be restarted using remote OFF followed by remote
ON.
Figure 2-9
Remote contact for 6EP3333-8SB00-0AY0 and 6EP3334-8SB00-0AY0