Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200 1ph
14
Manual, 11.2014, C98130-A7633-A1-3-7629
2.4
Status displays and signaling
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Operating display
④
LED green for "24 V O.K."
Yellow LED for overload in "constant current" mode
Red LED for latching shutdown in "shut down" mode
Signaling contacts (13, 14)
⑤
Relay contact (NO contact, contact rating 30 V AC / 0.5 A, 60 V DC / 0.3 A,
30 V DC / 1 A) for "24 V O.K.".
Figure 2-6
Operating display and signaling contact for 6EP3333-8SB00-0AY0 and
6EP3334-8SB00-0AY0
Signaling
6EP3333-8SB00-0AY0 (24 V/5 A)
6EP3334-8SB00-0AY0 (24 V/10 A)
Green LED lit
Signaling contact, contacts 13-14 closed
Normal operation, output voltage >20 V ±0.5 V
LED off
Signaling contact, contacts 13-14 open
(quiescent position)
No supply voltage
Yellow LED lit
Signaling contact, contacts 13-14 open
(quiescent position)
Overload, output voltage <20 V ±0.5 V (only in "constant current" mode)
Red LED lit
Signaling contact, contacts 13-14 open
(quiescent position)
Latching shut down or remote OFF