Technical data
6.5 Protection and monitoring
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629
39
6.5
Protection and monitoring
6EP1536-3AA00 (24 V/20 A)
Output overvoltage protection
< 33 V
Current limitation, typ.
22 A
Property of the output: short-circuit proof
Yes
Short-circuit protection
Optional constant current characteristic approx. 22 A or
latching shutdown
Continuous short-circuit current: rms value, typ.
•
Remark
22 A
Overload capability 150 % I
out rated
up to 5 s/min
Overload / short-circuit display
Yellow LED for "overload"
Red LED for "latching shutdown"
Overtemperature protection
LED red flashing for "Shutdown due to overtemperature"
6.6
MTBF
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Mean Time Between Failures
SN29500:> 620,000 h at 40 °C, rated
load, 24 h operation
> 10000000 h
6.7
Mechanical system
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Connection system
Screw-type terminal
Connections: Line input
DC input "+", "-", PE:
1 screw terminal each for 0.05 ... 4
(2.5) mm² solid (finely stranded)
DC input "+", "-", PE:
1 screw terminal each for 0.05 ... 4
(2.5) mm² solid (finely stranded)
Connections: Output
"+", "-", PE:
2 screw terminals each for 0.2 - 6
(4) mm² solid (finely stranded)
DC output "+", "-", PE:
1 screw terminal each for 0.05 - 4
(2.5) mm² solid (finely stranded)
Connections: Auxiliary contacts
Signaling contact:
2 screw terminals for 0.14 - 1.5 mm² solid
(finely stranded)
-
Width of the housing
90 mm
70 mm
Height of the housing
125 mm
125 mm
Depth of the housing
120 mm
120 mm
Mounting width
90 mm
70 mm
Mounting height
225 mm
225 mm
Summary of Contents for SITOP PSU400M
Page 8: ...Safety instructions SITOP PSU400M 8 Manual 05 2018 C98130 A7601 A1 5 7629 ...
Page 44: ...Safety approvals EMC 7 4 EMC SITOP PSU400M 44 Manual 05 2018 C98130 A7601 A1 5 7629 ...
Page 46: ...Ambient conditions SITOP PSU400M 46 Manual 05 2018 C98130 A7601 A1 5 7629 ...