SITOP PSU100L
Manual, 08.2016, C98130-A7603-A1-2-7629
31
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
SITOP PSU100L power supplies are designed for connection to a 1-phase AC line supply
(TN or TT system according to VDE 0100 T 300/IEC 364-3) with a rated voltage of
120/230 V AC, 50 - 60 Hz.
Figure 5-1
Line connection (example, 6EP1334-1LB00)
The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line connection
(example, 6EP1334-1LB00) (Page 31)), and must be implemented according to IEC 60364
and EN 50178 . A protective device (miniature circuit-breaker or circuit-breaker) and a
disconnection unit for the power supply must be provided. A ground-fault circuit interrupter is
not permissible against indirect contact as the only protective measure. This is true for the
complete line supply protected by the ground-fault circuit interrupter.
Summary of Contents for SITOP PSU100L 6EP1332-1LB00
Page 8: ...Safety instructions SITOP PSU100L 8 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 20: ...Mounting removal SITOP PSU100L 20 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 42: ...Technical data 6 8 Dimension drawing SITOP PSU100L 42 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 46: ...Safety approvals EMC 7 4 EMC SITOP PSU100L 46 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 56: ...Environment SITOP PSU100L 56 Manual 08 2016 C98130 A7603 A1 2 7629 ...