Applications
9
9.1
Parallel connection to increase power rating
To increase the power rating, SITOP modular power supplies of the same type can be
directly connected in parallel.
The following must be observed:
●
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
●
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
●
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
●
Switch change-over switch "A" (see Figure 2-8 Voltage selector switch (example,
6EP1334-3BA10) (Page 15)) to "Parallel operation".
Figure 9-1
Parallel connection