Typical circuit diagrams
10.1 Connection examples for main and control circuits
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
219
10.1.3
3RW44 in a standard circuit and DC braking stopping function for device types
3RW44 22 to 3RW44 25
Main circuit
Control circuit
1)
For permissible main and control voltage values, refer to chapter Technical data of the
power unit (Page 259).
Note
2)
Risk of restart
The start command (e.g. issued by the PLC) must be reset prior to issuing a reset command,
because the motor attempts to restart again automatically if a start command is still active
following this reset command. This particularly applies if the motor protection has tripped.
For safety reasons, you are advised to integrate the group fault output (terminals 95 and 96)
in the controller.
3)
If the "combined braking" stopping function is selected, a braking contactor is not required.
A braking contactor must be additionally used if the "DC braking" function is selected.
◆For types, refer to the "Feeder component layout (standard circuit)" table in chapter
component layout (standard circuit) (Page 270).
The "DC braking" function is recommended for applications with larger centrifugal masses
(J
load
> J
motor
).
Output 2 must be set to "DC braking contactor".