Starter combination
Direct-on-line starter
Reversing starter
Size
S00
S0
S2
S3
S00
S0
S2
S3
Mounting on 8US busbar with 60
mm busbar center-to-center spac‐
ing
With 8US busbar adapter
✓
✓
✓
—
✓
✓
✓
—
Screw mounting on base plate
Direct screw mounting on
mounting plate
✓
✓
✓
—
✓
✓
✓
—
Mounting on DIN-rail
adapter and screw mount‐
ing of the adapter on
mounting plate.
✓
✓
✓
✓
✓
✓
✓
✓
1)
Mounting on 1 DIN rail
2)
Mounting on 2 DIN rails
3)
For high vibration and shock loads: Mounting on 2 DIN rails and DIN-rail adapter
NOTICE
Possible damage to load feeder.
• If the load feeder for sizes S00 and S0 is mounted directly on the DIN rail without a DIN-rail
adapter, there is no guarantee that the mounting will be vibration-proof.
• Size S0 and S2 reversing starters have to be mounted with DIN-rail adapters or busbar
adapters.
• Size S3 reversing starters have to be mounted with DIN-rail adapters.
7.3.1
On DIN rails without DIN rail adapter
DIN rail mounting without adapter
Fuseless load feeders in the following sizes can be snapped onto DIN rails without adapters:
• Direct-on-line and reversing starters in size S00
• Direct-on-line starters in size S0 and S2
Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS 3RA Load Feeders
62
Equipment Manual, 02/2022, A5E03656507520A/RS-AC/004
Summary of Contents for SIRIUS 3RA
Page 26: ...Functions SIRIUS 3RA Load Feeders 26 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Page 120: ...Connection SIRIUS 3RA Load Feeders 120 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Page 122: ...Operation SIRIUS 3RA Load Feeders 122 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...