Appendix
A.8 Information List
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
304
2892
AR 4th cycle zone extension
release (AR 4.CycZoneRel)
Autoreclosure
OUT
*
*
*
LED
BO
40
172
1
No
2893
AR zone extension (general) (AR
Zone Release)
Autoreclosure
OUT
*
*
*
LED
BO
40
173
1
Yes
2894
AR Remote close signal send
(AR Remote Close)
Autoreclosure
OUT
*
ON
*
LED
BO
40
129
1
No
2895
No. of 1st AR-cycle CLOSE com-
mands,1pole (AR #Close1./1p=)
Statistics
VI
2896
No. of 1st AR-cycle CLOSE com-
mands,3pole (AR #Close1./3p=)
Statistics
VI
2897
No. of higher AR-cycle CLOSE
commands,1p (AR #Close2./1p=)
Statistics
VI
2898
No. of higher AR-cycle CLOSE
commands,3p (AR #Close2./3p=)
Statistics
VI
2901
>Switch on synchro-check func-
tion (>Sync. on)
Sync. Check
SP
*
*
*
LED BI
BO
2902
>Switch off synchro-check func-
tion (>Sync. off)
Sync. Check
SP
*
*
*
LED BI
BO
2903
>BLOCK synchro-check function
(>BLOCK Sync.)
Sync. Check
SP
*
*
*
LED BI
BO
2905
>Start synchro-check for Manual
Close (>Sync. Start MC)
Sync. Check
SP
on
off
*
*
LED BI
BO
2906
>Start synchro-check for AR
(>Sync. Start AR)
Sync. Check
SP
on
off
*
*
LED BI
BO
2907
>Sync-Prog. Live bus / live line /
Sync (>Sync. synch)
Sync. Check
SP
*
*
*
LED BI
BO
2908
>Sync-Prog. Usy1>Usy2<
(>Usy1>Usy2<)
Sync. Check
SP
*
*
*
LED BI
BO
2909
>Sync-Prog. Usy1<Usy2>
(>Usy1<Usy2>)
Sync. Check
SP
*
*
*
LED BI
BO
2910
>Sync-Prog. Usy1<Usy2<
(>Usy1<Usy2<)
Sync. Check
SP
*
*
*
LED BI
BO
2911
>Sync-Prog. Override ( bypass )
(>Sync. o/ride)
Sync. Check
SP
*
*
*
LED BI
BO
2930
Synchro-check ON/OFF via BI
(Sync. on/off BI)
Sync. Check
IntSP
ON
OFF
*
*
LED
BO
2931
Synchro-check is switched OFF
(Sync. OFF)
Sync. Check
OUT
ON
OFF
*
*
LED
BO
41
31
1
Yes
2932
Synchro-check is BLOCKED
(Sync. BLOCK)
Sync. Check
OUT
ON
OFF
ON
OFF
*
LED
BO
41
32
1
Yes
2934
Synchro-check function faulty
(Sync. faulty)
Sync. Check
OUT
ON
OFF
*
*
LED
BO
41
34
1
Yes
2935
Synchro-check supervision time
expired (Sync.Tsup.Exp)
Sync. Check
OUT
ON
ON
*
LED
BO
41
35
1
No
2936
Synchro-check request by control
(Sync. req.CNTRL)
Sync. Check
OUT
ON
ON
m
LED
BO
41
36
1
No
2941
Synchronization is running (Sync.
running)
Sync. Check
OUT
ON
OFF
ON
*
LED
BO
41
41
1
Yes
2942
Synchro-check override/bypass
(Sync.Override)
Sync. Check
OUT
ON
OFF
ON
*
LED
BO
41
42
1
Yes
2943
Synchronism detected (Synchro-
nism)
Sync. Check
OUT
ON
OFF
*
*
LED
BO
41
43
1
Yes
2944
SYNC Condition Usy1>Usy2<
true (SYNC Usy1>Usy2<)
Sync. Check
OUT
ON
OFF
*
*
LED
BO
41
44
1
Yes
2945
SYNC Condition Usy1<Usy2>
true (SYNC Usy1<Usy2>)
Sync. Check
OUT
ON
OFF
*
*
LED
BO
41
45
1
Yes
No.
Description
Function
Type
of In-
for-
matio
n
Log Buffers
Configurable in Matrix
IEC 60870-5-103
Ev
ent Log
O
N
/O
FF
T
rip (
F
aul
t)
Log On/
O
ff
G
round
Fault Log ON/
O
FF
M
a
rk
e
d
i
n
O
s
ci
ll.
Re
c
o
rd
LED
B
ina
ry
I
n
pu
t
Function
Key
Rela
y
Chatte
r Suppr
e
ssion
Ty
p
e
In
form
ati
on Nu
mbe
r
Dat
a
Un
it
Ge
ne
ra
l Int
e
rro
ga
ti
on
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...