2.5 Time Overcurrent Protection for Earth Current
179
7UT613/63x Manual
C53000-G1176-C160-2
2.5
Time Overcurrent Protection for Earth Current
2.5.1
General
The time overcurrent protection for earth current is assigned to a 1-phase measured
current input of the device. It can be used for any desired single-phase application. Its
preferred application is the detection of an earth current between the starpoint of a pro-
tective object and its earth electrode (that's why the description). The corresponding
one-phase additional measuring input has to be correctly assigned to the one-phase
current transformer of the power plant.
This protection can be used in addition to the restricted earth fault protection (Section
2.3). Then it forms the backup protection for earth faults outside the protected zone
which are not cleared there.
The time overcurrent protection for earth current provides two definite time stages (O)
and one inverse time stage (C). The latter may operate according to an IEC or an
ANSI, or a user defined characteristic.
Figure 2-77
Time overcurrent protection as backup protection for restricted earth fault pro-
tection
7UT613/63x is provided with two overcurrent functions for earth current, where each
can be used independent of each other at different locations. Assigning the different
protective functions to the one-phase measuring locations are according to Section
„Assigning the protective function to the measuring locations/sides“ performed.
2.5.2
Definite Time, Instantaneous Overcurrent Protection (UMZ)
The definite time stages (O) for earth current are always available even if an inverse
time characteristic has been configured in the scope of functions (see Subsection
2.1.3.1).
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...