Inverse-Time Overcurrent Protection (ANSI 51V)
51
7UM62 Manual
C53000-G1176-C149-3
Figure 2-18
Logic Diagram of the Voltage-Controlled Inverse O/C Time Protection
The changeover to the lower current pick-up value in case of decreasing voltage (loop
release) is performed on a phase by phase basis according to table 2-5.
Tripping
matrix
FNo. 01883
&
&
&
FNo. 01900
FNo. 01892
FNo. 01897
FNo. 01896
FNo. 01898
FNr. 000361
Fuse Failure
Loop
release
IL1
IL2
IL3
UL1
UL2
UL3
FNo. 01899
OR
OR
OR
TMin
TRIP CMD