3 Installation and Commissioning
332
7UM62 Manual
C53000-G1176-C149-3
3.1.3.4
Interface Modules
Exchanging
Interface Modules
The interface modules are located on the C–CPU–2 board (
Figure 3-12 shows the p.c.b. with the location of the modules.
Figure 3-12
C–CPU–2 board with Interface Modules
Please observe the following:
•
The interface modules can only be exchanged in devices for panel flush mounting
and cubicle mounting.
Devices for panel surface mounting with two-tier terminals can only be converted in
the factory.
•
You can fit only those interface modules that are also part of the standard
configurations of the device as specified in the Ordering Data in the Appendix A.1.
B
D
Mounting position
(rear of housing)
Analog output
System interface
or analog output