3.1 Installation and Connections
331
7UM62 Manual
C53000-G1176-C149-3
Jumpers X71, X72 and X73 on the I/O-6 board are used to set the bus address and
must not be changed. Table 3-17 shows the factory setting of the jumpers.
Note:
The jumper settings must correspond to the mode set at addresses
(volt-
age or current input) and
0297
(with/without filter). If they do not, the device is blocked
and outputs an alarm. After any changes to the jumper settings, you should therefore
immediately change the corresponding parameter settings using DIGSI
®
4.
Table 3-17
Factory Jumper Setting on the I/O-6 Board
Jumper
Factory Setting
X71 (AD0)
1–2 (H)
X72 (AD1)
2–3 (L)
X73 (AD2)
1–2 (H)
Note:
Measuring transducers that are not used should be shorted at the input terminals.