Functions
280
7UM62 Manual
C53000-G1176-C149-3
Influence on
Protective
Functions
The swapping of phases directly impacts the calculation of positive and negative
sequence quantities, as well as phase-to-phase voltages via the subtraction of one
phase-to-ground voltage from another. Therefore, this function is vital so that phase
detection messages, fault values, and operating measurement values are not falsified.
As stated before, this function influences the unbalance load protection function,
directional overcurrent protection function, and some of the monitoring functions
(see Subsection 2.38.1.3), that issue messages if the required and calculated phase
rotations do not match.
2.43.2 Setting Hint
The normal phase sequence has been set at the address
(see Section 2.3).
If, on the system side, phase rotation reversal is performed temporarily, then this is
communicated to the protective device via the binary input ”
(FNo.