Functions
238
7UM62 Manual
C53000-G1176-C149-3
2.36.2.1 Settings of the DC Voltage Protection
2.36.2.2 Information from the DC Voltage Protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
7201
DC PROTECTION
OFF
ON
Block relay for trip com-
mands
OFF
DC Voltage/Current Protection
7202
MEAS.METHOD
Mean Value
Root Mean Square
Mean Value
Measurement Method (MEAN/
RMS Values)
7203
DC >/<
DC Voltage/Current Stage
DC >
DC Voltage/Current Stage
DC <
DC Voltage/Cur-
rent Stage DC >
Method of Operation (DC >/<)
7204
U DC ><
0.1..8.5 V
2.0 V
DC Voltage Pickup
7205
I DC ><
0.2..17.0 mA
4.0 mA
DC Current Pickup
7206
T DC
0.00..60.00 sec;
∞
2.00 sec
Time Delay for Trip of DC Pro-
tection
F.No.
Alarm
Comments
05293 >BLOCK DC Prot.
>BLOCK DC protection
05301 DC Prot. OFF
DC protection is switched OFF
05302 DC Prot.BLOCKED
DC protection is BLOCKED
05303 DC Prot. ACTIVE
DC protection is ACTIVE
05307 DC Prot. TRIP
DC protection TRIP
05306 DC Prot.pick.up
DC protection picked up
05308 Failure DC Prot
Failure DC protection