Out-of-Step Protection (ANSI 78)
147
7UM62 Manual
C53000-G1176-C149-3
2.18.2.2 Information for the Out-of-Step Protection
3510
REP. CHAR. 2
1..8
4
Number of Power Swing: Cha-
racteristic 2
3511
T-HOLDING
0.20..60.00 sec
20.00 sec
Holding Time of Fault Detection
3512
T-SIGNAL
0.02..0.15 sec
0.05 sec
Min. Signal Time for Annun.
Char. 1/2
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
05053 >BLOCK O/S
>BLOCK out-of-step protection
05061 O/S OFF
Out-of-step protection is switched OFF
05062 O/S BLOCKED
Out-of-step protection is BLOCKED
05063 O/S ACTIVE
Out-of-step protection is ACTIVE
05067 O/S char. 1
Out-of-step pulse of characteristic 1
05068 O/S char. 2
Out-of-step pulse of characteristic 2
05069 O/S det. char.1
Out-of-step characteristic 1 picked up
05070 O/S det. char.2
Out-of-step characteristic 2 picked up
05071 O/S TRIP char.1
Out-of-step TRIP characteristic 1
05072 O/S TRIP char.2
Out-of-step TRIP characteristic 2