4 Technical Data
330
7UM61 Manual
C53000-G1176-C127-3
4.16 90-%-Stator Earth Fault Protection (ANSI 59N, 64G, 67G)
Setting Ranges / Increments
Times
Dropout Ratio / Dropout Difference
Tolerances
Influencing Variables
Displacement Voltage U
Earth
2.0 V to 125.0 V
Increments 0.1V
Earth current I
Earth
2 mA to 1000 mA
Increments 1 mA
Earth current angle criterion
0
°
to 360
°
Increments 1
°
Delay Time T
SEF
0.00 s to 60.00 s
or
∞
(ineffective)
Increments 0.01 s
The set times are pure delay times.
Pickup Times
U
Earth
I
Earth
directional
approx. 50 ms
approx. 50 ms
approx. 70 ms
Dropout Times
U
Earth
I
Earth
directional
approx. 50 ms
approx. 50 ms
approx. 70 ms
Displacement voltage U
Earth
approx. 0.70
Earth current I
Earth
approx. 0.70
Angle criterion (dropout difference)
10
°
towards network
Displacement Voltage
1 % of setting value or 0.5 V
Earth current
1 % of setting value or 0.5 mA
Delay times T
1 % of setting value or 10 ms
Power Supply DC Voltage in Range
0,8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Frequency in Range
0,95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
≤
1 %
≤
1 %
www
. ElectricalPartManuals
. com