Commissioning
269
7SS52 V4 Manual
C53000-G1176-C182-3
Figure 7-7 Dialog box devices in/outputs
−
Example
Changing the oper-
ating state
To change the operating state of a hardware component, click the corresponding
panel in the column
Nominal
.
Before executing the first change of the operating state the password No. 6 is demand-
ed (provided that it has been activated). After entering the correct password, the op-
erating state change is executed. Further state changes remain released until the di-
alog box is closed.
Testing the output
relays
You can energize every single output relay to check the wiring between the output re-
lay of the central unit and the system without having to create the alarm allocated to
it. As soon as you have initiated the first state change for any output relay,
all
output
relays are disconnected from the functionality of the device and can only be operated
by the hardware test function. This means, that e.g. a TRIP command coming from a
protection function or a control command from the operator panel to an output relay
cannot be executed.
Make sure that the operations initiated by the output relays can be made without
any dangers.
Test every output relay via the corresponding
Nominal
box of the dialog box.
Finish the tests (see margin title below “Finishing the process“), so that during fur-
ther testing no unwanted switching operations are initiated.