Technical Data
4.1 General Device Data
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
308
Output Relays
1)
FLA = “Full Load Ampere”
Output Relay for Commands/Annunciations, Alarm Relay
*
)
Number and Information
According to the Order Variant (allocatable);
Values in ( ): up to release .../DD
Order variant
NO contact
NO/NC, switch selectable
7SJ610*–
2 (4)
3 (1)
7SJ611*–
6 (8)
3 (1)
7SJ612*–
4 (6)
3 (1)
Switching capability CLOSE
1000 W/VA
Switching capability TRIP
30 VA 40 W resistive 25 W
at L/R
≤
50 ms
Switching voltage
250 VDC / 250 VAC
Admissible current per contact (continuous)
5 A
Adm. current per contact (close and hold)
30 A for 0.5 s (NO contact)
Total Current on common path
5 A continuous, 30 A for 0.5 s
AC Load
(it has to be taken into consideration for the dimensions of external circuits)
Value of the ANSI capacitor:
4,70· 10
-9
F
±
20%
Frequency
Impedance
50 Hz
6,77· 10
5
Ω
±
20%
60 Hz
5,64· 10
5
Ω
±
20%
*
) UL–listed with the following nominal values:
120 VAC
Pilot duty, B
240 VAC
Pilot duty, B
240 VAC
5 A General Purpose
24 VDC
5 A General Purpose
48 VDC
0.8 A General Purpose
240 VDC
0.1 A General Purpose
120 VAC
1/6 hp (4.4 FLA
)
240 VAC
1/2 hp (4.9 FLA
)