Technical Data
10-10
7SA522 Manual
C53000-G1176-C119-2
10.1.9 Certifications
UL listing
Models with threaded terminals
7SA522
∗
–
∗
A
∗ ∗ ∗
–
∗ ∗ ∗ ∗
7SA522
∗
–
∗
C
∗ ∗ ∗
–
∗ ∗ ∗ ∗
7SA522
∗
–
∗
D
∗ ∗ ∗
–
∗ ∗ ∗ ∗
UL recognition
Models with plug-in terminals
7SA522
∗
–
∗
J
∗ ∗ ∗
–
∗ ∗ ∗ ∗
7SA522
∗
–
∗
L
∗ ∗ ∗
–
∗ ∗ ∗ ∗
7SA522
∗
–
∗
M
∗ ∗ ∗
–
∗ ∗ ∗ ∗
10.1.10 Construction
Housing
7XP20
Dimensions
see drawings, Section 10.18
Weight (mass) (max. complement) approx.
– in flush mounted case, size
1
/
2
6 kg (13.2 pounds)
– in flush mounted case, size
1
/
1
10 kg (22.0 pounds)
– in surface mounted case, size
1
/
2
11 kg (24.3 pounds)
– in surface mounted case, size
1
/
1
19 kg (41.9 pounds)
Degree of protection acc. IEC 60529
– for the device
in surface mounted case
IP 51
in flush mounted case
front
IP 51
rear
IP 50
– for human safety
IP 2x with closed protection cover
10.2
Distance Protection
Earth Impedance
Matching
R
E
/R
L
–0.33 to 7.00
(steps 0.01)
X
E
/X
L
–0.33 to 7.00
(steps 0.01)
separate for first and higher zones
K
0
0.000 to 4.000
(steps 0.001)
PHI (K
0
)
–135.00° to +135.00°
(steps 0.01)
separate for first and higher zones
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...